How to read a valve datasheet: ratings, dimensions and certificates
A practical guide to reading valve datasheets: PN/DN ratings, pressure-temperature tables, face-to-face dimensions, material certificates to EN 10204 and what pressure test records actually certify.
A valve datasheet is a contract in miniature. Every number on it — the pressure rating, the face-to-face dimension, the material grade, the certificate type — either protects the project or quietly transfers risk to whoever signed the purchase order without reading it. This guide walks through the sections of a typical industrial valve datasheet in the order a reviewing engineer should read them, with the common misreadings that cause rework.
Start with the identification block
The first block identifies the valve unambiguously: manufacturer, type (gate, globe, check, ball, butterfly), the series or figure number, and the nominal size and pressure class. Read the pressure class notation carefully, because it encodes two different standard families:
- PN ratings (EN/European practice): PN10, PN16, PN25, PN40 — the nominal pressure class in bar at a reference temperature, tied to EN pressure-temperature tables and metric flanges to EN 1092-1.
- Class ratings (ASME/American practice): Class 150, 300, 600 — tied to ASME B16.34 pressure-temperature ratings and inch-based flanges to ASME B16.5.
PN and Class are not convertible by a single factor. A Class 150 valve is roughly comparable to PN20 at moderate temperatures, not PN16, and the relationship shifts with temperature because the two rating tables use different materials and curves. Never substitute “PN16 = Class 150” on a datasheet; check the actual P/T tables for the body material at the design temperature.
The pressure-temperature (P/T) table: the real rating
The single most misread section is the pressure-temperature table. The PN or Class number is a name, not a constant operating rating — the actual permissible pressure falls as temperature rises, along material-specific curves. A PN40 grey cast iron valve, a PN40 carbon steel valve and a PN40 stainless valve have different curves and different temperature ceilings.
Read it this way:
- Find the body material row (cast iron, WCB carbon steel, CF8M stainless, etc.).
- Find the design temperature column of your line — the highest it will ever see, including upset and steam-out conditions, not just normal operation.
- Read the allowable pressure at that temperature. That value, not the class name, is what the valve is rated for in your service.
Two traps: first, the P/T table often lists ratings for several materials, and reviewers read the row above or below their own material. Second, the table gives allowable pressure at temperature, not a duty cycle — continuous operation at 100% of the tabulated rating with zero margin leaves nothing for transients. Good practice keeps normal operating pressure comfortably below the tabulated limit.
Also note the minimum temperature limit: carbon steel bodies commonly carry a minimum around -29 °C in standard grades; impact-tested grades are needed for lower temperatures. Cryogenic or low-temperature service requires explicit confirmation, not assumption.
Nominal size: DN and NPS
Datasheets quote size as DN (metric, e.g. DN100) or NPS (inch, e.g. NPS 4). DN100 and NPS 4 refer to the same nominal point in most standard series, but the pairing matters for flanges: a DN100 PN16 flange to EN 1092-1 and an NPS 4 Class 150 flange to ASME B16.5 have different bolt counts, bolt diameters and drilling circles in many cases. A valve that is “the same size” but on the wrong flange system does not bolt up. Confirm the flange standard explicitly — it is its own line item on any serious datasheet, and mixing DN sizes with Class flanges on one enquiry is a common source of wrong goods.
Face-to-face and end-to-end dimensions
Face-to-face (FTF) is the distance between the gasket faces of the two end connections; for wafer and lug bodies, the relevant dimension is the face-to-face of the body between the flange faces it is clamped between, per ASME B16.10 (or the applicable standard). The FTF dimension decides whether the valve physically fits an existing pipe gap — and each standard series (gate, globe, check, ball, butterfly) has different FTF values at the same DN.
Practical rules:
- Never assume two valve types of the same size share an FTF. Globe and gate valves of the same DN differ; butterfly valves are much shorter than gate valves.
- For a replacement in an existing line, measure the installed gap and compare against the datasheet FTF before ordering; retrofit spacers or a different body series are cheaper than a valve that does not fit.
- Note whether the datasheet gives FTF, end-to-end (for welded ends) or both. Butt-weld valves need end-to-end including the weld bevel ends.
Materials section
The materials block lists body, bonnet/cover, obturator (wedge, disc, ball, plug), seat, stem and packing/gasket materials, usually by standard designation: e.g. ASTM A216 WCB for cast carbon steel, ASTM A351 CF8M for cast austenitic stainless, EN-GJL-250 for grey cast iron, or Chinese GB equivalents. For a comprehensive cross-reference of casting grades across DIN/EN and ASTM, see our technical reference on valve body material codes explained. For multi-brand sourcing across dedicated product catalogues, consult the INDSCM brand matrix.
Read for three things:
- Consistency with the P/T table: the material named in the materials block is the one whose P/T curve applies. If the datasheet lists “WCB or GG-25 depending on variant”, the two have different ratings and different media compatibility — the order must specify which.
- Trim hardness: for abrasive or cavitation service, seat and obturator hardness (e.g. 13Cr, hardfaced) is the detail that decides life.
- NACE/ sour service: if the medium is sour (H₂S), confirm whether the materials and hardness limits meet NACE MR0175/ISO 15156. This is a separate statement on the datasheet, not something implied by stainless trim.
Certificates: what EN 10204 3.1 and 3.2 actually mean
Material certificates follow EN 10204, and the type number defines who certifies what:
| Certificate type | Issued by | Content | Typical use |
|---|---|---|---|
| 2.1 | Manufacturer, statement | Declaration of compliance with the order, no test results | Non-critical commodity valves |
| 2.2 | Manufacturer, with test results | Statement plus specific test results, non-specific testing | General industrial duty |
| 3.1 | Manufacturer’s authorized inspection representative independent of the manufacturing department | Specific test results on the actual delivered product | Pressure equipment, standard for PED-affected valves |
| 3.2 | Manufacturer’s representative and the purchaser’s representative, or an independent inspection body | Specific tests witnessed by both parties | Critical/high-hazard service, offshore, third-party inspected projects |
Two practical points: a 3.1 certificate is the normal requirement for valves supplying into pressure equipment directive jurisdictions — state it explicitly in the order, because it carries cost and manufacturers will ship 2.1/2.2 by default unless 3.1 is requested. And a 3.2 certificate requires advance arrangement: the purchaser’s representative or third party must be present or engaged at the works; it cannot be “upgraded” after delivery.
The certificate traces the pressure-retaining materials — body, bonnet, obturator where pressure-retaining, bolting. Seats, packing and gaskets typically carry less formal documentation unless specified.
Pressure test records
Valves receive a shell (hydrostatic) test, typically at 1.5× the rated pressure at the test temperature, and a seat leakage test per a stated standard — most commonly API 598 for API-series valves, ISO 5208 (rate A, B, C, D, etc.) for industrial valves, or EN 12266-1 (rate A–F) in European practice. Read the test section for:
- Which shell test pressure applies (relative to the P/T-corrected rating, not the class name).
- Which seat leakage rate is certified: “leakage rate A” (ISO 5208 / EN 12266-1) means no visible leakage during the test duration — it is not an absolute-zero claim, and it differs from API 598’s drop-based leakage allowances for elastic-seat vs metal-seat valves.
- Test medium (water, air, or both) — low-pressure air seat tests matter for gas service.
- Whether a functional/operating torque test is included.
A datasheet that says only “tested to standard” without a leakage rate is incomplete; state the required rate in the order.
Marking and documentation package
The final sections cover nameplate marking (per EN 19 or ASME B16.34: manufacturer, size, class, material, body marking, flow direction) and the documentation the shipment carries. A well-specified order asks for: certificate type per EN 10204, test reports with leakage rate, operation and maintenance manual, and, for regulated jurisdictions, conformity documentation. Collecting this list once into a standard enquiry text saves negotiation on every order.
Conclusion
A valve datasheet rewards a fixed reading order: identify the valve and its true P/T rating at design temperature, confirm size and flange system, check face-to-face against the actual pipe gap, verify materials against the medium (and sour service if relevant), pin the certificate type to EN 10204 3.1 where pressure-equipment rules apply, and read the leakage rate — not just the words “tested”. Every one of these points has a standard behind it, and quoting the standard in the purchase order is what turns a datasheet from marketing into a specification.
FAQ
How does PN16 compare to Class 150?
No. PN and Class follow different rating systems with different temperature curves. Class 150 is closer to PN20 at moderate temperatures, and the relationship changes with temperature and material. Always compare the pressure-temperature tables for the actual body material at design temperature.
What is the difference between EN 10204 3.1 and 3.2 certificates?
A 3.1 certificate is issued by the manufacturer’s own inspection representative, independent of production, with test results specific to the delivered product. A 3.2 additionally requires the purchaser’s representative or a third-party inspector to witness the tests — it must be arranged before manufacture and costs more.
What seat leakage rate should I specify?
For most industrial duty, leakage rate A per ISO 5208 or EN 12266-1 is the standard tightness requirement. API 598 is the customary test for API-series valves and uses different, drop-based allowances that differ between soft-seat and metal-seat valves. Name the standard and rate in the order.
Why doesn’t my valve fit the old pipe gap?
Face-to-face lengths differ between valve types and standards at the same nominal size. Globe and gate valves of the same DN have different FTF, and butterfly valves are much shorter. Measure the installed gap and compare with the datasheet before ordering a replacement.
What does “leakage rate A” actually guarantee?
Rate A (ISO 5208 / EN 12266-1) means no visible leakage during the specified test duration at the specified test pressure. It is a defined acceptance criterion, not a claim of absolute zero leakage, and it is measured under test conditions that may differ from operating conditions.